
Volume 4, Issue 2
May 2002
Solvent
Purification
Introduction
Traditionally,
chemists and other laboratory workers who require extremely high purity
solvents were forced to purify these solvents by reflux at elevated temperatures,
over water-reactive drying agents (Li, Na, K, CaH2, LiAlH4). Over the
years, there have been many fires and explosions involving thermal distillation
apparatus. Chemists characterize thermal distillation as one of the most
dangerous routine procedures they perform.
In 1996, Pangborn,
et al 1 published in the journal, Organometallics, an alternative to thermal
distillation. In 2001, Alaimo, et al 2 published in the Journal of Chemical
Education, suggested modifications to the apparatus described by Pangborn.
The so-called "Grubbs apparatus" uses a large solvent reservoir
and alumina/catalyst columns to dry and de-oxygenate solvents to the desired
level of purity; without using heat or water-reactive drying agents. Stakeholders
(Fire Departments, researchers, health and safety professionals, to name
but a few) are very interested in reducing the risk of fire, explosion,
injury, and property damage inherent in thermal distillation. A major
goal in the development of this Guideline is to significantly reduce or
eliminate the routine use of thermal methods.
Basis for Requirements
In consultation
with industry experts, system-wide Industrial Hygiene & Safety Committee
UC faculty and staff, and the system-wide Industrial Hygiene & Safety
Committee, the UC Fire Marshals Group has developed the following Guideline.
The intent of this Guideline is to encourage the replacement of thermal
methods, as traditional stills will no longer be approved, with safer
methods while ensuring compliance with applicable Fire Code, Mechanical
Code, Electrical Code, Building Code, Cal/OSHA regulations, and good laboratory
safety practices. This Guideline is intended to provide the basis for
the design, planning, installation, and operation of Grubbs apparatus
for solvent purification in University of California facilities.
Use
For the purposes
of this Guideline, the column solvent purification apparatus will be referred
to as the Grubbs apparatus. Others might use the terms "push still,"
"column purification," or "Grubbs still." The Grubbs
apparatus consists of a stainless steel solvent reservoir, (typically
18 liters), one alumina column, one catalyst on alumina column, and a
purified solvent delivery port. The reservoir is pressurized (to less
than 10 psi) with an inert gas (typically nitrogen or argon), and the
solvent is pushed out of the reservoir, through the columns to an evacuated
glass flask or delivered directly to the experiment. Columns and reservoirs
can be set up in parallel, with carefully labelled valves, to purify several
solvents on demand. A small vacuum pump maintains negative pressure on
the manifold and collection flasks, and exhausts inert gas at the end
of the apparatus.
All
plans, specifications, standard operating procedures, and operational
protocols must be approved by the campus Fire Marshal, in consultation
with EH&S.
Guideline
System
Constuction
- The reservoir
container size must be no greater than 19 liters. Most chemical manufacturers
provide 18 or 19 liter containers of high purity solvents, already stored
under inert gas. These containers have been pressure-tested and many
have the appropriate fittings for connection to the Grubbs apparatus.
Homemade reservoir containers, such as those made from empty propane
bottles, are not permitted.
2001 CFC, Table 7902.1-A
- When fully assembled
on site, a final pressure check of the apparatus shall be performed.
Pressure check requirements are described in Section 1406.2.2 of the
California Mechanical Code (2001)
- All solvent reservoir
containers shall be stored in flammable liquid storage cabinets.
Section 7902.5.9 of the CFC (2001).
- All solvent transfer
tubing and fittings shall be stainless steel.
Refer to the requirements of Section 7901.11 of the CFC (2001) for additional
details.
- All valves and
tubing shall be clearly labeled in accordance with the requirements
of ANSI A13.1, 1996 edition.
- A system piping
and instrumentation diagram (P&ID) must be submitted to the Fire
Marshal for review.
- Arrows shall be
used to indicate the direction of the flow.
- Piping should
be color-coded. Labeling of the contents of the piping should be applied
as close to the color bands as possible.
- Color identification
must be consistent throughout the system.
- Install low volume
quick disconnects on the top of the solvent reservoir and on the purification
columns to minimize spillage during change out procedures.
- All apparatus
and ancillary equipment must be seismically braced.
Section 1634A of the CBC (1998).
- The vacuum pump
is an integral component of some versions of the Grubbs apparatus, to
maintain negative pressure on the system and exhaust gas and vapors.
The vacuum pump exhaust must be metallic and ducted to the fume hood
exhaust or general laboratory exhaust. Pump exhaust shall not be returned
to the building. Some versions of the Grubbs apparatus, because of where
the purified solvent is delivered, do not require a vacuum pump. An
apparatus set up to deliver solvent directly into a glove box does not
require a vacuum pump.
- The Grubbs apparatus
must be installed on a dished work surface, similar to the work surface
of a chemical fume hood, capable of containing a small, incidental spill.
Secondary containment is integral to flammable liquid storage cabinets,
which are required for storage of the solvent reservoir(s). Any plumbing
from the solvent reservoir, through the work surface into the apparatus
must be sealed with fire resistant caulk (i.e., FireStop) or sealed
with the appropriate bulkhead fitting.
- The room, laboratory
or area where the Grubbs apparatus are placed shall have a clear and
unobstructed exit. Aisle width may not be less than 36 inches.
CBC (2001), section 1007.4, section 304.2.2.11 and section 307.4
Check CBC section 1004.3.2 - aisle width may be required to be greater,
depending on occupancy, location of exit doors, and how the space is
arranged.
- Specifications,
from the apparatus' designer and/or manufacturer, plans for installation
conforming to the manufacturer's instructions and this Guideline must
be submitted to the Campus Fire Marshal for review and approval.
Local
Exhaust Ventilation
For
new facilities, the Grubbs apparatus must be installed in a fume hood
or other, 3-sided exhausted enclosure (i.e., backdraft exhaust system)
with a minimum of 25 cfm per square foot of internal work surface. For
existing facilities, if it is not possible to install the apparatus in
an exhausted enclosure, the general exhaust in the laboratory must be
at least 10 air changes per hour, with the Grubbs apparatus installed
so that good dilution ventilation is possible. If not installed in a fume
hood or 3-sided enclosure, the apparatus must be installed and used in
a well-ventilated laboratory and not in a converted closet or storage
room. NFPA 45, A.6.4.6.
Electrical Safety
- Based on the California
Electrical Code, 2001, section 500-7 (b), the Grubbs apparatus meets
the definition of a Class 1, Division 2 location. The vacuum pump installed
on the apparatus must meet the requirements of section 501-8 (b) and
be located apart from the apparatus - outside of the exhausted enclosure
or away from the flammable liquid storage cabinets is optimum. An explosion-proof
vacuum pump, designed to be used in areas where there are flammable
vapors, may be used next to the Grubbs apparatus.
Details describing distances are in Section 500 of the CEC (2001) and
Article 79, CFC (2001).
- An emergency shut-off
switch or valve must be provided, to prevent any uncontrolled release
from the solvent reservoir, should the apparatus develop a leak. Consideration
should be given to an emergency vent valve (in addition to the emergency
shut-off valve), to release pressure on the apparatus, should the apparatus
develop a leak.
- The Grubbs apparatus
and solvent reservoirs must be properly grounded and bonded. If quick
connect fittings are used, make sure the fittings are electrically bonded.
Alarms, Fire Detection, and Suppression
The
Grubbs apparatus must be installed in a location with an automatic smoke
detection system that is interconnected with the building fire alarm system.
For new facilities, automatic fire suppression must be applied. For existing
facilities, consideration should be given to local fire suppression at
the apparatus installation. An ABC fire extinguisher (with a minimum rating
of 3A:40BC) must be available within 10 feet of the apparatus.
System
Operation
- If the system
is not installed in a ventilated enclosure, personal protective equipment
and corresponding care must be used appropriate to the hazards of the
solvents when disconnecting the columns for reactivation or replacements.
The current exposure limits for many common solvents (benzene, dichloromethane,
etc.) are quite low and may require respiratory protection during non-routine
operations.
- If the solvent
reservoir needs to be re-filled, the solvent transfer must be done in
a fume hood. A pump with proper, anti-static tubing, must be used for
transferring solvents from large (>5 gallons) containers.
- The Principal
Investigator, in consultation with the Grubbs apparatus designer and/or
manufacturer, must prepare a laboratory and equipment specific Standard
Operating Procedure addressing reservoir filling, solvent degassing,
apparatus operation, dispensing, etc., for the safe operation of the
apparatus. The SOP's and design document (P&ID) will be used as
training tools to facilitate the Principal Investigator's training of
end users.
- A written SOP
must also be developed for activation of the column beds. If the resin
beds will be reused, a regeneration procedure must be developed.
- All users of the
Grubbs apparatus must participate in safety and operation training and
read and follow all written SOP's. All training must be documented and
maintained by the department.
- All Grubbs apparatus
must adhere to manufacturer's installation instructions and Campus Fire
Marshal/Environmental Health and Safety direction.
Vendors
and References
Glass
Contour: http://www.glasscontour.com
Innovative Technology: http://www.solventpurification
Pangborn,
A.B., Giardello, M.A., Grubbs, R.H., et al; Organometallics, 15(5), 1518-1520,
1996.
Alaimo, Peter
J.; Peters, David W.; Arnold, John; Bergman, Robert G.; J. of Chem. Ed.
2001 78 64.
Additional
information may be obtained by calling the UC Davis Fire Department at
(530)752-1236.
|